国产人妻人伦精品一区二区_69堂亚洲国产日韩精品无码专区成人妻中文字幕一区二区三区在线久久久久_人妻中文字幕无码专区

Fluorescent Optical Fiber Temperature Measurement Solution for Power Contact in Power Grid Industry

Fluorescent Optical Fiber Temperature Measurement Solution for Power Contact in Power Grid Industry

1. Systematic Introduction

Transformers, switchgears, large motors and other high-voltage electrical equipment are the key equipment of power generation and transmission and transformation systems. Their safety, reliability and service life are crucial to the safe and reliable operation and life of the entire transmission and transformation system. Most of these high-voltage equipment are enclosed structure. They work in the environment of high voltage, high current and strong magnetic field for a long time. Some joints are heated due to aging or excessive contact resistance, which results in heat accumulation. Heating temperature rise increases the loss of power transmission system. If the heat dissipation is not good, it will endanger the normal operation of equipment, even cause faults. The adverse social impact and economic losses are immeasurable.

Taking transformer as an example, the accident rate of distribution transformer in operation is about 13%, in which the insulation aging is caused by the over temperature operation of windings, and the burnout and breakdown accidents of transformer windings account for a considerable proportion. In addition, many physical and chemical changes (such as partial discharge and partial overheating) in power transformer will cause the temperature parameters of transformer to change, which makes the temperature rise track of transformer different from that of normal operation. Based on the relationship between the aging rate and temperature of transformer according to the "6°rule" , the life of transformer can be reduced by half when the aging rate increases by one time at 6℃, and the life of transformer can be prolonged by one time when the temperature decreases by 6℃. For transformers, winding temperature plays a decisive role in the aging of insulation materials, so it is particularly important to accurately measure the winding temperature of transformers. With the continuous improvement of the automation level of safe power consumption and distribution network, besides monitoring the electrical parameters, direct monitoring of hot-spot temperature of high-voltage electrical equipment such as transformer/switchgear/transformer/large motor can improve the safe operation of equipment, prolong the insulation life of equipment, instantly judge the actual load capacity of equipment, and maximize the potential of transformer transmission and transformation to improve the installation. The economic benefits of preparation are of great significance.

The applications of fluorescent optical fiber temperature sensor in smart grid are as follows:

1. Power transformer winding temperature monitoring;

2. High-voltage switchgear: It can measure the temperature of plum blossom contacts and static contacts in switchgear, and even bury them in the conductive connection of insulating cylinder;

3. Temperature measurement of arc extinguishing chamber of high voltage circuit breaker;

4. Temperature monitoring of stator, bush and end confluence ring of large motor;

5. Direct monitoring of hot spot temperature of high voltage equipment such as large motor/transformer windings;

6. Other electrical equipment temperature online real-time monitoring.

image.png

 

As one of the future development directions of optical fiber temperature sensor, fluorescent optical fiber temperature sensor for smart grid also has the following advantages:

1. Immunization to electromagnetism, radio frequency and microwave;

2. No metal parts, no magnetization;

3. The measurement accuracy is high and the stability is good;

4. Good reliability and repeatability;

5. Structural tightness, long service life;

6. No calibration is required.

Compared with traditional temperature sensors, optical fiber temperature sensors have incomparable advantages. With the maturity of optical fiber temperature sensor technology and the establishment of technical regulations and related standards, fluorescent optical fiber temperature sensors will gradually replace traditional temperature sensors and become one of the most important means of temperature monitoring in power grid.

Fluorescent optical fiber temperature sensor is one of the key equipment in future smart grids. Developing smart grid industry based on various smart sensors is the extension and expansion of developing green new energy industry in China. It is a realistic need to combine China's industrial base, accelerate the transformation and upgrading of power equipment manufacturing industry, adapt to future competition, and achieve sustainable development. It is an inevitable choice for the high-end market and technological commanding point of power grid industry to strive for greater development space. It is an effective way and carrier to accelerate the integration of industrialization and information technology. It has very important practical significance and long-term strategic significance for stimulating economic development, optimizing industrial structure and transforming development mode.

 

2. Technical Advantages

The comparison of several main temperature measurement methods in the field of electric power at present:

2.1 Infrared Thermal Imaging Temperature Measurement System

Advantages:

1. Non-contact temperature measurement, and easy to operate;

2. Low cost.

Disadvantages:

1. The measurement is inaccurate, only the surface temperature can be measured; the real temperature of the internal hot spot cannot be measured;

2. Handheld, and cannot achieve online monitoring;

3. Artificial inspection, increase labor costs, the minimum annual labor costs of more than 100,000 Yuan.

2.2 Wireless Temperature Measurement System

Advantages:

1. Easy installation;

2. Low cost.

Disadvantages:

1. Poor reliability, with battery measurement, short life;

2. The insulation performance of cabinet is affected, so it cannot pass the test;

3. The large volume of the sensor affects the heat dissipation function;

4. The surface temperature can only be measured, but the real temperature inside the hot spot cannot be measured.

2.3 Fiber Bragg Grating Temperature Measurement System

Advantages:

1. Quasi-distributed temperature measurement can be realized, which is suitable for long-distance and large-area areas;

2. With optical fiber technology, the insulation performance is good.

Disadvantages:

1. Difficult to install;

2. Cannot achieve a single cabinet matching, cannot achieve in-situ display.

2.4 Fluorescent Optical Fiber Temperature Measurement System

Advantages:

1. Its performance is safe and reliable, and it can achieve calibration-free, good consistency, interchangeability and stability;

2. Long service life, maintenance-free. Minimum use of optical fiber sensors for 25 years;

3. The probe is small in size and can be used to measure the hot spot in depth, so as to realize the real and effective monitoring of the hot spot;

4. Anti-electromagnetic interference, good insulation performance, integrated into intelligent switchgear and passed the type test;

5. It can be displayed locally and integrated into the control system conveniently.

6. Easy installation and flexible networking;

7. High cost performance ratio.

Disadvantages:

1. The measuring distance is relatively short, usually in the order of 100 meters.

For the node temperature measurement of electrical equipment in power plants and substations, Herch’s fluorescent optical fiber temperature measurement has obvious advantages: no electrical interference, small size, long life, independent networking, and high reliability.

 

3. System Characteristics

Guarantee the ideal isolation of primary and secondary power, good linearity and high accuracy;

Multichannel transmission: The information collected by the system can be uploaded and dispatched by FTU, GPRS or communication management unit in the box, and the transmission mode can be flexibly selected according to the field environment;

Do not reduce the safety level of electrical equipment: Temperature-measuring fluorescent optical fiber fire detector is small, 2.8mm in diameter, without any metal materials, electronic components, good insulation, 20cm withstands 100,000 volts voltage;

Full-year, all-weather security guardian: At least 25 years, 365 days a year, 24 hours a day real-time monitoring and analysis;

It reduces the blind area of monitoring and improves the safety of equipment: Positioning accuracy is 1 mm;

Cost savings: Directly installed in the temperature rise part, real-time recording and displaying monitoring point data to achieve unattended monitoring station objectives;

Maintenance basis is established: Fully grasp the operation of the equipment, can predict the aging of the equipment, so as to put forward the maintenance time and maintenance plan according to the operation status of the equipment;

Intelligent judgment: It can quickly judge and analyze the normal temperature, abnormal temperature and fire of the tested object.

 

4. Major Performance Indicators

image.png

image.png

 

5. Introduction of Main Components

The HQ series fluorescent optical fiber temperature monitoring system is selected as the on-line monitoring system for electric power connection in rail transit industry. A set of system is mainly composed of several optical fiber temperature sensors, a multi-channel optical fiber demodulator, monitoring host computer and human-machine exchange software.

5.1 HQ Series Fluorescent Fiber Temperature Demodulator

HQ series fluorescent optical fiber temperature demodulator receives real-time optical signal with temperature information from temperature-measuring fluorescent optical fiber fire detector, and demodulates it to temperature value to realize temperature measurement of monitored parts. When the actual measurement value is larger than the alarm setting value, the alarm signal sent out. They can work independently on a single computer, or can be used in multiple networking, and are suitable for application requirements of various scales.

5.2 Temperature-Measuring Fluorescent Optical Fiber Fire Detector

The probe size of temperature-measuring fluorescent fiber-optic fire detector is very small and can be directly installed at the measured point, which can measure temperature accurately and respond quickly. Its tail fiber is made of soft and strong special optical fiber, which has the advantages of high transmission bandwidth, stable signal, anti-electromagnetic interference, anti-flexure, high impact strength and fast connection.

The tail fiber sheath has the characteristics of high temperature resistance, aging resistance, corrosion resistance, high insulation, non-adherence and so on. It can adapt to the harsh environment of high voltage, high temperature, strong electromagnetic and so on.

5.3 Monitor Host

The monitoring host can receive and process the normal information, fault information and disaster information from the optical fiber temperature demodulator in real time, and quickly process and manage them. The monitoring host has the functions of fault monitoring, display, alarm and information exchange. At the same time, the remote monitoring can be realized through the network.

5.4 Men-Machine Interface

The main functions of the software system include real-time temperature local monitoring, real-time data remote monitoring, high/low temperature alarm, high/low temperature early warning, historical data playback, pre-alarm and post-alarm curve, temperature export to Excel and other functions.

6. Construction cases

Installation of monitoring host: The monitoring host of this system is installed in the monitoring cabinet of the substation control room, and a monitoring computer is set up in the central control station for remote monitoring.

Installation of HQ Series Optical Fiber Temperature Demodulator: The demodulator is installed on the back wall of the instrument panel in front of the switchgear to facilitate future maintenance.

image.png

image.png

Schematic Diagram of the Layout of the Switchgear in the HQ Series Fluorescent Optical Fiber Temperature Monitoring System

Installation of HQ-12 Temperature-measuring Fluorescent Optical Fiber Sensor

1. Installation on Switchgear Contacts

image.png

The main hotspot of switchgear is located at the joint of static and dynamic contacts, but this part is protected by insulating sleeve, and the space inside is very narrow. In order to measure the heating temperature of contacts more accurately, the diameter of HQ-12 temperature-measuring fluorescent optical fiber sensor is 2.8mm. It can extend into the inner of the sleeve from the rear of the sleeve along the confluence row. A high temperature resistant and high insulation installation clamp is designed specifically for the static contacts, which can fix the sensor firmly on the static contacts. 

When fixing the fluorescent optical fiber fire detector with a clamp, the sensor head is fixed in the fixed groove of the sensor first, and then the clamp and the sensor head are clamped on the cylinder of the static contact. During installation, the clamp is installed at the joint of the static contact and the bus bar to keep a safe distance from the movable contact.

2. Installation at Cable Joint of Switchgear

The fluorescent optical fiber fire detector for temperature measurement was pasted on the cable joint with special aviation silica gel and fixed with special strapping.

image.png

After the installation of the temperature-measuring fluorescent optical fiber fire detector is completed, the tail fibers are tied to the copper bars connected with the rear of the static contacts with insulating straps to prevent the temperature-measuring fluorescent optical fiber probe from hitting the adjacent contacts in case of falling off.

Inside Cabinet Wiring

In order not to affect the electrical distribution in the cabinet, as well as the future overhaul of the cabinet, cables and tail fibers in the cabinet should be as far as possible along the corner of the cabinet, or take a special trunk or bundle with the secondary cable in the cabinet.

image.png

HQ series transformer winding temperature measurement system, the optical fiber sensor probe is installed in winding coil in the process of transformer fabrication. Through flange penetrator, the internal and external optical signals are docked, and the temperature measurement host is analyzed and demodulated to realize real-time on-line temperature measurement.

Background communication: Real-time temperature data of field power equipment are uploaded to the backstage monitoring system through 485 parallel lines or optical cable transmission.

About insulation and anti-creeping: Temperature-measuring fluorescent optical fiber fire detector has high insulation, anti-creeping, anti-corrosion.

 

Attachment: Product Model

image.png

A股新纪录!今年以来上市公司现金分红总额达2.61万亿 创历史新高 兴业银行行长陈信健:价值银行“扎根越深” 估值方能“枝繁叶茂”|银行 如何消化天量国债?日本政府盯上了普通家庭7万亿美元“钱袋子”|日本 油价或下调,就在今晚|成品油 “历史铸就共同体——西藏地方与祖国关系史专题展”在京开幕 全球肺癌关注月 中际旭创:光引擎作为光模块的核心部件,均为公司自主设计和生产|中际旭创 攀登脑机接口“珠峰”,这群“海归”希望为盲人带来光明 周期顺风、通胀回落、AI动荡、波动保护---这是高盛2026年“10大核心主题交易” 高峰:大模型选型就是“选择适合自己的AI”,选对路径才能实现从“+AI”到“AI+”的范式重塑 招商银行:给予招商局集团1650亿元综合授信额度,授信期限3年 中国拟立托育服务法 禁止托育人员实施侵害婴幼儿身心健康的行为 日本防卫大臣小泉进次郎赴长崎视察部队 主张加强西南防卫 金风科技赚钱“密术”:前两年投资收益超主业,今年又押中25倍牛股|金风科技 工银投资等在湖南成立空天海洋产业发展基金 出资额30亿 博威合金:截止目前,公司航空航天业务仅获悉航空航天专用合金线材的销量同比增长38%以上|星座 不得对现金支付采取歧视性措施!三部门规范各类现金收付行为|规定 中国机器人在格斗机器人大赛中夺冠 利好加持!这一板块强势上涨,多股飙升!|新能源车 壁仞科技(06082)招股,23名基石投资认购29亿,将成2026年首家香港上市公司,1月2日挂牌 【维权】涉嫌信息披露违法违规等事项 卓然股份及实控人被立案 维权征集启动|卓然 牛弹琴:最终,欧洲还是没敢|欧盟